Article

Determination Of Safety Distances From Ground Electrodes Subjected To Impulse Conditions

arrow_icon

Usman Muhammad, Fazlul Aman, Normiza Mohamad Nor, Syarifah Abdullah

arrow_icon

DOI: 10.15598/aeee.v22i1.5336

Abstract

When a high magnitude of current is discharged to the ground, a large potential gradient will result in a ground potential rise (GPR, or induced voltage. This GPR usually decreases with distances, depending on the soil resistivity, ground electrode sizes, configurations and steady state resistanceRDC values. The GPR value not only provides an information on the safe distance of the nearby equipment to the grounded electrical systems subjected to impulse conditions, but can also identify the right rating of the equipment, particularly sensitive electronic equipment, that are in a vicinity of the ground installations. Further, during the high voltage testing on the ground electrodes at field sites, the results may also be influenced by the electrodes under tests, which can cause inaccuracy in the measurements. This paper is therefore aimed to measure the GPR, where the measured results are still found to be limited in literature, for various soil resistivity and ground electrodes. The measured GPR values are obtained by injecting high magnitudes of impulse current of both impulse polarities on the ground electrode, and the voltage magnitudes at distances away from the edge of the electrode under impulse are measured. The measurements of GPR allows the investigations on the effect of impulse polarity on these GPR values, which cannot be obtained by computational method.

Full Text:

PDF

Cite this